DVP-120 Installation & Operating Instructions

Strona 2

Revision 0.07 10 2.3 Main power Connection The main power cable should be routed into the bottom left conduit entry. Macurco recommends a minimum wi

Strona 3

Revision 0.07 11 Each 8-terminal sensor modular connector may be disconnected from the PCB connector to ease wire installation. The terminals will acc

Strona 4

Revision 0.07 12 2.5 Relay Connection All poles of the three relays are available at the modular connector J2 (see Figure 2-2 for details). J2 is a 9

Strona 5 - 1 INTRODUCTION

Revision 0.07 13 2.6 Horn & Strobe Connection The external horn and strobe connections are available at the modular connector J5 (see Figure 2-3

Strona 6 - Revision 0.07

Revision 0.07 14 2.7 Interfacing Macurco Sensors All Macurco CO, NO2 and combustible gas sensors with current loop outputs may be used with the DVP-1

Strona 7

Revision 0.07 15 3 Operation 3.1 Initial Operating Mode When power is first applied to the DVP-120, a few simple tests will be performed, e.g. cycle

Strona 8 - 1.4 Specifications

Revision 0.07 16 3.1.2 User Interface The LCD display is used to show detailed information about the status of the control system and the configurat

Strona 9

Revision 0.07 17 3.1.3 Normal Status Display MO N 1 0 : 2 3 R 1 O F F S 0 1 C O 5 P P MFigure 3-4 Normal System Display The display shows

Strona 10 - 2.3 Main power Connection

Revision 0.07 18 A L A R M S I L E N C E D F O R 5 M I N U T E S Figure 3-7 Alarm Silenced message If Relay 1 has be configured as an ALARM r

Strona 11

Revision 0.07 19 When the HUSH key is pressed, the internal buzzer will be silenced for eight (8) hours. If the horn or strobe turn on delays have not

Strona 12 - 2.5 Relay Connection

Revision 0.07 2 TABLE OF CONTENTS 1 INTRODUCTION ...

Strona 13

Revision 0.07 20 3.3 Setting the System Configuration The configuration menus can be entered from normal mode by pressing the MENU key. While in conf

Strona 14

Revision 0.07 21 3.3.1 System Menu The top menu level allows the user to select: – Configure System – Configure Sensors – Configure Relays, Horn &

Strona 15 - 3.1 Initial Operating Mode

Revision 0.07 22 3.3.2.2 Set Day of Week T i m e : 2 2 : 5 5 D a y : 2 T u e s d a y Figure 3-19 Set Day of the week This display example s

Strona 16

Revision 0.07 23 3.3.2.4 Enter Password P a s s w o r d * * * * Figure 3-21 Enter Password ? This display shows that the passwor

Strona 17

Revision 0.07 24 3.3.3 Configure Sensors Submenu There is a list of parameters for each sensor in the system, either currently wired or configured bu

Strona 18

Revision 0.07 25 3.3.3.4 Warning Set Point S e n s o r 0 1 C O Wa r n i n g : _ _ 5 0 p p m Figure 3-27 Sensor’s Warning Level The default war

Strona 19 - 3.2 Ventilation control

Revision 0.07 26 3.3.4 Configure Relays, Horn & Strobe Submenu There is a list of parameters for each relay in the system. The left and right cur

Strona 20

Revision 0.07 27 3.3.5 Configure Horn Submenu The configuration parameters for the horn are the same as those for relays. A horn would not normally r

Strona 21

Revision 0.07 28 3.3.6 Configure Strobe Submenu The configuration parameters for the strobe are the same as those for relays. A strobe would not nor

Strona 22

Revision 0.07 29 3.3.7 Configure Zones Submenu The DVP-120 ventilation control can support up to three zones. The zone functionality makes the DVP-12

Strona 23

Revision 0.07 3 Figure 3-4 Normal System Display...

Strona 24

Revision 0.07 30 3.3.7.3 Timed Day Selection Z 1 G r o u p 1 T i m e d D a y s : 1 We e k d a y s Figure 3-43 Timer Days Selection Valid entries

Strona 25

Revision 0.07 31 3.3.7.7 Rising Trip Point Z 1 G r o u p 1 N O 2 R i s i n g : 2 . 5 p p m Figure 3-48 Rising Trip Point Entry The default ri

Strona 26

Revision 0.07 32 3.3.8 Configure Signals Submenu The DVP-120 can drive the buzzer, horn and strobe with different sound patterns to indicate the seve

Strona 27

Revision 0.07 33 3.3.8.4 Alarm Strobe Signal A l a r m S i g n a l s S t r o b e : 1 C o n t i n . Figure 3-55 Strobe Alarm Signal This display

Strona 28

Revision 0.07 34 S t r o b e : 5 O F F Figure 3-59 Strobe Warning Signal This display example shows that the strobe will not signal a warning con

Strona 29

Revision 0.07 35 3.3.8.12 Trouble Strobe Signal T r o u b l e S i g n a l s S t r o b e : 5 O F F Figure 3-63 Strobe Trouble Signal This displa

Strona 30

Revision 0.07 36 4 Troubleshooting The DVP-120 is extensively tested at the factory to ensure reliable operation. Most problems can be traced to the

Strona 31

Revision 0.07 37 4.3 No Power WARNING 120/240 VAC terminals are located within the DVP-120, presenting a hazard to service technicians. Only qualifi

Strona 32

Revision 0.07 4 LIST OF TABLES Table 2-1 Main Power Connections ...

Strona 33

Revision 0.07 5 1 INTRODUCTION 1.1 General Information The DVP-120 Gas Detection and Ventilation Control Panel is a microcomputer based control pan

Strona 34

Revision 0.07 6 CM-2BD CB-A+outputpowercoilcoilExhaust Fans120 VACALARM120 VACPowerMain Fan PowerSTARTER RELAYS120 VAC COILSMACURCO DVP-120GAS DETECTI

Strona 35

Revision 0.07 7 Figure 1-2 DVP-120 Internal View

Strona 36 - 4 Troubleshooting

Revision 0.07 8 1.4 Specifications1 – Size: 10” x 12” x 2” (254 mm x 305 mm x 51 mm) – Weight: TBD – Enclosure: Nema 1 equivalent steel – Operatin

Strona 37 - WARNING

Revision 0.07 9 2 Installation & Connection 2.1 Mounting the DVP-120 Mounting holes are provided in the DVP-120 case at the four corners. The t